Input definition – type Area
(INPUT/OUTPUT, 1,
)
INPUT DEFINITION
State
:false
Input
:1
Trig.
:latched
Type
:Area
Mode
:active
Area
:1
continuous
Fct.
:Fire
Event
unlogged
0. .9,
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Input/Output Menu
Page 109
Place cursor at TYPE
Select Type: AREA and press
(Unlock memory!)
Select the Function
*See Common Facilities - All Input Types, Page 111 for description of Input, State,
Trigger, Mode, Event and Text
An area is defined as a group of zones
(see Page 99)
. An input can be assigned to an
area by specifying the area number and the function.
List of Functions:
Fire
Fault
Coincidence
Condition
Disable
Pre Warning
-
An area coincidence is two or more zones allocated to the area in a fire alarm condition.
It is independent of zones in coincidence. *See Page 99
Trigger:
Latched/Unlatched
Mode:
Passive/Active
Always continuous
Event:
Always unlogged
Text:
Not applicable
* See Input Description in the Serial Communication Format