Example 2
Output:
1
Link:
SND
Mode:
Zone
Zone:
11
This is a zone Sounder Output.
:
In EP mode the output switches ON.
In EN/NEN/Vds mode the output switches ON
only if it was silenced before.
:
The output is disabled.
:
The output is only switched after the Sounder
Delay has elapsed.
FIRE IN ZONE 11
:
The output switches ON.
SILENCE
:
The output switches OFF.
TEST
:
The output switches to Test Mode.
SOUND
DISABLE
DELAY ON/OFF
Summary of Contents for FP2000