Input definition – type Zone
(INPUT/OUTPUT, 1,
)
INPUT DEFINITION
State
:false
Input
:1
Trig.
:latched
Type
:Zone
Mode
:active
Zone
:1
continuous
Fct.
:Fire
Event
unlogged
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Input/Output Menu
Page 109
Place cursor at TYPE
Select Type: ZONE and press
(Unlock memory!)
Select the Function
*See Common Facilities - All Input Types, Page 111 for description of Input, State,
Trigger, Mode, Event and Text.
Inputs can be activated by zones for the following functions. For this type the zone
number must also be specified.
List of Functions:
Fire
Fault
Coincidence
Condition
Disable
Pre Warning
Trigger:
Latched/Unlatched
Mode:
Passive/Active
Always continuous
Event:
Always unlogged
Text:
Not applicable
* See Input Description in the Serial Communication Format