Modem alarm report 2
(MODEM ALARM REPORT 1,
)
MODEM ALARM REPORT
Fire Delay
:60 s
Report
:dis
Fault Delay
:60 s
Test Call
:dis
Cond. Delay
:60 s
Test Line
:dis
more
0. . 9,
^V,
<>,
E,
X
Alarms: 0
Faults: 1
Cond.: 0
P: 1
SDZ
Return to Modem Menu
Page 45
Select field to be changed
To change selection (Unlock memory!)
Confirm entry
Press
to go back to Modem Alarm Report 1
Page 46
Fire, Fault and Cond. Delay:
Delays reporting to control station. If the panel gets reset before the delay has elapsed,
no alarm/fault condition will be reported. The shortest delay will start the reporting to the
central station and will report all pending alarms/faults/conditions.
Report:
Instead of report disabling by using the previous menu (Modem Alarm Report 1), this
menu supplies a quick disable mechanism. Disabling reports on this menu will disable all
reports regardless of the setup on the previous menu (Modem Alarm Report 1).
Test Call:
This menu enables a test call at every maintenance time.
Test Line:
This menu enables a line test with hardware test, manually or every hour automatically.