Backpanel and Frontpanel Input and Output Equipped -
The FP2000 contains, as standard, relays and input ports. The back panel refers to the
boards plugged into the FEP section in the base of the fire panel. The front panel refers
to the boards plugged into the HOST section in the door of the fire panel. The HOST
section contains two layers of board plug-in positions.
The standard equipped I/O is:
•
Four Inputs IN1 - IN4 located on the FEP board -
These inputs are freely programmable by the user.
•
Sounder board:
- Four
supervised
relays (OUT1 - OUT4)
- Four
non-supervised
relays (OUT5 - OUT8)
The
supervised
relays have dedicated functions:
OUT1
-
Sounder
OUT2
-
Fire Brigade
OUT3
-
Fire Protection
OUT4
-
Fault Routing
- Four supervised inputs (IN5 - IN8)
IN8 is a general programmable input, but the others have dedicated functions:
IN5
-
Fire brigade feedback (VdS-mode only)
IN6
-
Fire protection fault (VdS-mode only)
IN7
-
Fault routing fault (VdS-mode only)
All relays are programmable by means of the I/O programming menus, but care should
be taken when programming the dedicated relays above.
Any additional optional I/O that is equipped within the FP2000 will be shown on this
screen.
*See I/O Menus, Page 109 for the programming of Inputs and Outputs.