Panels
(NETWORK, 1,
)
PANELS
Panel No.
:1
Status
:dis
Start Zone
:1
End Zone
:255
0. . 9,
^V,
<>,
E,
X
Alarms: 0
Faults: 0
Cond.: 0
P: 1
SDZ
Return to Network Menu
Page 41
or 0..9 to select panel number
Move to status field
Toggle dis/NET1 check/NET2 check/ NET1 no check/NET2 no check (Unlock
memory!)
Confirm entry
The fire panels that will communicate with this FP2000 fire panel on the network must be
assigned.
Fire panels that are assigned to the network will be checked for communication on the
system. If a panel is assigned to "NET1/2 check", a fault warning will be displayed in the
event of a failure, but if assigned to "NET1/2 no check" the failure will only be an action
logged in the event buffer.
-
Each fire panel on the system must have the correct ID set
(see Page 35).
The fire panel that is being programmed must be set at disable, i.e. a fire panel does not
check itself: assign only
other
fire panels.
If the functionality is set to global zone repeater, each panel has a start and an end zone
assigned. Zones ranges can not be overlapping.