xx = term/assignment number
yy is used for timer assignment only
Expressions may contain any number of terms separated by operators, but only up to
nested expressions. Each term is separated by either an "(" or operator or operator ")".
Assignment can be Output, Marker or Timer.
The operators available are:
END
Delete*
Insert*
NULL
)=
) set-s
) reset-s
) set-e
) reset-e
AND
AND NOT
AND (
AND NOT (
OR
OR NOT
OR (
OR NOT (
(
NOT (
)
)
*INSERT and DELETE are editing functions and are used at the time of entering.
The Term/Assignments available are:
Input
xx
Output
xx
Marker
xx
Timer
xx
not Input
xx
not Output
xx
not Marker
xx
not Timer
xx
xx - parameter of term
Input
xx
=
1 to maximum Input Table
Output
xx
=
1 to maximum Output Table
Marker
xx
=
1 to 250
Timer
xx
=
1 to 250
yy time of timer = 1 to 240 seconds
-
When timer is used as an assignment, then the time yy is specified. When the timer is
used as a term in an expression, then the true/false state of the timer is used.