Alarm device disable
(DEVICE DISABLE MENU, 1,
)
ALARM DEVICE DISABLE next
Address
:1/1
Status
:en
State
:NML
Zone
:0
Type
:OPT
Value
:34
Day Lv1
:2
PreLv1
:90
AlarmLv1 :110
^V,
<>,
E,
X
Alarms: 0
Faults: 1
Cond.: 0
P: 1
SDZ
Return to Device Disable Menu
Page 190
Toggle between DISABLE/ENABLE/SOAKTEST
Confirm entry
This screen allows the disabling of devices currently in fire alarm or fault condition and
enabling those devices already disabled.
For disabling/enabling
any
device on the system, *See Manual Device Disable Page 192
.
The most recent highest priority device in alarm is displayed. By moving the cursor to the
‘next’ field and pressing ENTER, the other devices in alarm may be selected. The status
field is toggled to disable, soak test or enable. The current alarm condition will not be
removed until the fire panel is reset.
Disable does not electrically disconnect the device from the loop
. Disable should not
be used if maintenance is to be done on the loop or the devices. The loop must be
physically disconnected in this case.
The zone, state, type and value are displayed for information purposes.
*See Device Setup (Page 79) for further information.