870
16 POSITIONING INSTRUCTION
16.1 Dedicated Instruction (Positioning Function)
Processing details
This instruction executes one-speed positioning by incremental drive. Specify the positioning address in the incremental
system, in which the transfer direction and transfer distance from the current position (relative address) are specified for
positioning.
• For (s1), specify the relative positioning address in user units. (The address must be within the range of -2147483647 to
+2147483647 number of pulses.)
• For (s2), specify the command speed in user units. (The speed must be 200 Kpps or lower in frequency.)
• For (d1), specify the device from which pulses are output. Only the Y devices having positioning parameters can be
specified.
• For (d2), specify the device from which the rotation direction signal is output. Only the device specified with the parameter
or general-purpose outputs can be specified. When the output devices (Y) is executed by another function (PWM,
positioning PULSE axis, or CW/CCW axis etc.), the device does not function and causes an error.
For details on the function, precautions, and error code, refer to
MELSEC iQ-F FX5 User's Manual (Positioning Control -
CPU module built-in, High-speed pulse input/output module).