ABB ABILITY™ SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS 
JANUARY 2019

PRODUCT GUIDE

SSC600

Summary of Contents for ABILITY SSC600

Page 1: ...ABB ABILITY SMART SUBSTATION CONTROL AND PROTECTION FOR ELECTRICAL SYSTEMS JANUARY 2019 PRODUCT GUIDE SSC600...

Page 2: ...a commitment by ABB ABB assumes no responsibility for any errors that may appear in this document Copyright 2019 ABB All rights reserved Trademarks ABB and Relion are registered trademarks of the ABB...

Page 3: ...a tor transformer blocks in utility and industry power distribution systems Once the device has been given the application specific settings it can directly be put into service 2 Protection functions...

Page 4: ...w ohmic and higher ohmic earth faults and for transient and intermittent or restriking earth faults SSC600 also features optional arc fault protection of the circuit breaker busbar and cable compartme...

Page 5: ...rrent and residual voltage based on the received process bus measurements The residual voltage The phase voltages The voltage sequence components Frequency The device also calculates the demand value...

Page 6: ...me stamps The non volatile memory retains its data even if the device temporarily loses its auxiliary supply The event log facilitates detailed pre and post fault analyses of feeder faults and disturb...

Page 7: ...e supports simultaneous event reporting to five different clients on the station bus The device can exchange data with other devices using the IEC 61850 protocol The device can send binary and analog...

Page 8: ...supports the following high accuracy time synchro nization method with a timestamping resolution of 4 s required especially in process bus applications PTP IEEE 1588 v2 with Power Profile IEEE 1588 v...

Page 9: ...ns Description Value Operating temperature range 20 55 C continuous Short time Short time service temperature range 25 70 C 16h 1 2 Relative humidity 95 non condensing Atmospheric pressure Altitude Tr...

Page 10: ...ard Vibration response and endurance test 6 10 1 Class 1 IEC 60255 21 1 Shock response test 6 10 2 Class 1 IEC 60255 21 2 Shock endurance test 6 10 2 Class 1 IEC 60255 21 2 Bumb test 6 10 2 Class 1 IE...

Page 11: ...PTOC 40 200000 ms 10 Operating curve type 6 PHLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 PHHPTOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 PHI...

Page 12: ...1 10 In 5 0 of the set value at currents in the range of 10 40 In Start time 11 12 EFIPTOC IFault 2 set Start value IFault 10 set Start value Minimum Typical Maximum 16 ms 11 ms 19 ms 12 ms 23 ms 14...

Page 13: ...ange Step Start value DEFLPDEF 0 010 5 000 In 0 005 DEFHPDEF 0 10 40 00 In 0 01 Directional mode DEFLPDEF and DEFHPDEF 1 Non directional 2 Forward 3 Reverse Time multiplier DEFLPDEF 0 05 15 00 0 01 DE...

Page 14: ...metric based earth fault protection WPWDE Characteristic Value Operation accuracy Current and voltage 1 5 of the set value or 0 002 In Power 3 of the set value or 0 002 Pn Start time 2526 Typically 63...

Page 15: ...20 ms Reset time Typically 40 ms Reset ratio Typically 0 96 Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode...

Page 16: ...Minimum Typical Maximum 62 ms 66 ms 70 ms Reset time Typically 40 ms Reset ratio Depends on the set Relative hysteresis Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the s...

Page 17: ...5 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 Table 37 Positive sequence undervoltage protection PSPTUV ma...

Page 18: ...of the set value or 30 ms Table 41 Frequency protection FRPFRQ main settings Parameter Function Value Range Step Operation mode FRPFRQ 1 Freq 2 Freq 3 df dt 4 Freq df dt 5 Freq df dt 6 Freq OR df dt 7...

Page 19: ...TTR 0 05 4 00 In 0 01 Temperature rise T1PTTR 0 0 200 0 C 0 1 Time constant T1PTTR 60 60000 s 1 Maximum temperature T1PTTR 20 0 200 0 C 0 1 Alarm value T1PTTR 20 0 150 0 C 0 1 Reclose temperature T1PT...

Page 20: ...tection ARCSARC Characteristic Value Operation accuracy 3 of the set value or 0 01 In Operate time Operation mode Light current 45 46 Minimum Typical Maximum 9 ms 47 4 ms 48 12 ms 47 6 ms 48 15 ms 47...

Page 21: ...based earth fault protection MFADPSDE Characteristic Value Operation accuracy 1 0 of the set value or 20 ms 1 5 of the set value or 0 002 Un Start time56 Typically 35 ms Reset time Typically 40 ms Ope...

Page 22: ...racteristic Value Operation accuracy Depending on the frequency of the measured current fn 2 Hz 1 5 of the set value or 0 002 In Start time Typically 300 ms Reset time Typically 40 ms Reset ratio Typi...

Page 23: ...stall 4 IIt stall CB Restart inhibit time STTPMSU 0 250 min 1 Table 68 Phase reversal protection PREVPTOC Characteristic Value Operation accuracy Depending on the frequency of the measured current fn...

Page 24: ...0 002 x In at currents in the range of 0 01 4 00 x In Operate time accuracy 57 2 0 of the theoretical value or 0 50 s Table 73 Three phase thermal overload protection two time constants T2PTTR main s...

Page 25: ...impedance restricted earth fault protection LREFPNDF Characteristic Value Operation accuracy Depending on the frequency of the measured current fn 2 Hz 2 5 of the set value or 0 002 x In Start time 60...

Page 26: ...racy Depending on the frequency of the measured current and voltage fn 2 Hz Reactive power range PF 0 71 Power 3 0 or 0 002 Qn Voltage 1 5 of the set value or 0 002 Un Start time 62 63 Typically 46 ms...

Page 27: ...VRTPTUV 0 00 1 20 ms 0 01 Voltage level 5 LVRTPTUV 0 00 1 20 ms 0 01 Voltage level 6 LVRTPTUV 0 00 1 20 ms 0 01 Voltage level 7 LVRTPTUV 0 00 1 20 ms 0 01 Voltage level 8 LVRTPTUV 0 00 1 20 ms 0 01 Vo...

Page 28: ...ain settings Parameter Function Value Range Step Live dead mode SECRSYN 1 Off 1 Both Dead 2 Live L Dead B 3 Dead L Live B 4 Dead Bus L Any 5 Dead L Bus Any 6 One Live Dead 7 Not Both Live Difference v...

Page 29: ...measurement CSMSQI Characteristic Value Operation accuracy Depending on the frequency of the measured current f fn 2 Hz 1 0 or 0 002 In at currents in the range of 0 01 4 00 In Suppression of harmonic...

Page 30: ...e voltages in range 0 50 1 15 Un At the frequency fn 1 Hz 1 5 for apparent power S 1 5 for active power P and active energy 67 1 5 for reactive power Q and reactive energy 68 0 015 for power factor Su...

Page 31: ...splay offer front panel user interface functionality with menu navigation and menu views In addition WHMI includes a user configurable single line diagram SLD with position indication for the associat...

Page 32: ...ser Internet Explorer 8 0 9 0 10 0 and 11 0 SSC600 Connectivity Package 1 0 or later Table 102 Supported functions Function Web HMI PCM600 Device parameter setting Saving of device parameter settings...

Page 33: ...earth fault protection high stage DEFHPDEF1 Io 1 67N 2 1 Admittance based earth fault protection EFPADM1 Yo 1 21YN 1 Wattmetric based earth fault protection WPWDE1 Po 1 32N 1 Transient intermittent ea...

Page 34: ...60617 IEC ANSI Current total demand distortion CMHAI1 PQM3I 1 PQM3I 1 Voltage total harmonic distortion VMHAI1 PQM3U 1 PQM3V 1 Voltage variation PHQVVR1 PQMU 1 PQMV 1 Voltage unbalance VSQVUB1 PQUUB 1...

Page 35: ...1 SCA4 1 SCA4 1 Integer value move MVI4GAPC1 MVI4 1 MVI4 1 28 Order form Table 110 Order code example Order code digits 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 S B A C A N A N A A A 1 A N N 1 1G Tab...

Page 36: ...nits relays A Communica tion A 9 or A Z A B No additional communication cards Ethernet 1000Base SX 2 x LC with PRP A Communica tion protocol A 9 or A Z A IEC 61850 A Language 1 9 1 English 1 Table 113...

Page 37: ...l overvoltage protection ROVPTOV 8 Three phase undervoltage protection for 10 feeders across 4 bus sections PHPTUV 40 Three phase overvoltage protection for 10 feeders across 4 bus sections PHPTOV 8 P...

Page 38: ...0 Name Number of Instances OR gate with two inputs OR2 800 OR gate with six inputs OR6 400 OR gate with twenty inputs OR20 200 AND gate with two inputs AND2 800 AND gate with six inputs AND6 400 AND g...

Page 39: ...information GOOSERCV_ENUM 200 29 2 Feeder Application Package Feeder Application Package can be selected with order code Digit 4 and it can be selected for 5 10 15 or 20 feeders The size of the packa...

Page 40: ...ault locator SCEFRFLO 5 10 15 20 Directional reactive power under voltage protection DQPTUV 5 10 15 20 Low voltage ride through protection LVRTPTUV 15 30 45 60 29 4 Transformer Application Package Tra...

Page 41: ...TTPMSU 5 10 15 20 Phase reversal protection PREVPTOC 5 10 15 20 Thermal overload protection for motors MPTTR 5 10 15 20 29 6 Special Application Package Special optional applications can be selected w...

Page 42: ...reserved Specifications subject to change without notice Document ID 1MRS758725 ABB Distribution Solutions Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 4...