7 BASIC INSTRUCTIONS
7.7 Data Transfer Instructions
355
7
Processing details
• These instructions block transfer the 16-bit binary data of (n) number of devices starting from the one specified by (s) to the
device specified by (d).
• If the device number range is exceeded, data is transferred within the possible range.
• Data can be transferred even when the device range of the transfer-source device and transfer-destination device is
overlapping. To transfer data to a device having a smaller device number, transfer from (s), and to transfer data to a device
having a larger device number, transfer from (s)+(n)-1.
Ex.
When transferring data to a device having a smaller device number
When transferring data to a device having a larger device number
Precautions
• To perform nibble specification of bit device for both (s) and (d), be sure to set the same number of nibbles for (s) and (d).
• To use a module access device for (s) and (d), specify either (s) or (d).
Operation error
Error code
(SD0/SD8067)
Description
3405H
The number of nibbles of the nibble specification of bit device of (s) and (d) is different.
3420H
A module access device is specified for both (s) and (d).
∙∙∙
∙∙∙
(n)
1234H
5678H
7FF0H
6FFFH
1234H
5678H
7FF0H
6FFFH
553FH
553FH
(n)
b15
b0
(s)
(s)+1
(s)+(n-2)
(s)+(n-1)
(s)+2
(d)
(d)+1
(d)+2
(d)+(n-2)
(d)+(n-1)
∙∙∙
b15
b0
∙∙∙
1)
2)
3)
D9
D10
D11
D10
D11
D12
X1
BMOV
D10
D9
K3
3)
2)
1)
D11
D12
D13
D10
D11
D12
X2
BMOV
D10
D11
K3
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......