1070
30 TIMER FUNCTION BLOCKS
30.2 On-delay Timer
■
Operation result
1.
Function block without EN/ENO
The following table lists the operation results.
• Timing chart
2.
Function block with EN/ENO
The following table lists the execution conditions and operation results.
• Timing chart
Operation error
Operation result
(d1), (d2)
No operation error occurred
Operation output value
An operation error occurred
Indefinite value
When T#5s (5 seconds) is specified in n
(1): When (s) is on, the time measurement of (d2) starts.
(2): When (d2) reaches the time specified by n, (d1) turns on.
(3): On the falling edge of (s), (d2) is reset.
Execution condition
Operation result
EN
ENO
(d1), (d2)
TRUE (Executes operation)
TRUE (Operation error did not occur)
Operation output value
FALSE (Operation error occurred)
Previous output value
FALSE (Stops operation)
FALSE
Previous output value
When T#5s (5 seconds) is specified in n
(1): When EN and (s) are on, the time measurement of (d2) starts.
(2): When (d2) reaches the time specified by n, (d1) turns on.
(3): When EN is on and (s) is off, (d1) turns off and (d2) is reset.
Error code
(SD0/SD8067)
Description
3401H
The set value of the output time exceeds the effective range.
OFF
OFF
ON
ON
(s)
OFF
OFF
ON
(d1)
(d2)
(1)
(2)
(3)
0
3
2
2
3
4
1
1
0
0
0
0
5
OFF
ON
ON
ON
ON
ON
EN
OFF
OFF
ON
OFF
ON
(s)
ENO
OFF
OFF
ON
0
0
1
2
3
4
5
0
(d1)
(d2)
(1)
(2)
(3)
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......