330
7 BASIC INSTRUCTIONS
7.5 Data Conversion Instructions
Processing details
• "0" to "F" (hexadecimal numbers) in low-order 4 bits (1 digit) of (s) are decoded to data for the seven-segment display unit,
and stored in the low-order 8 bits of (d). Low-order 8 bits of (d) are occupied, and high-order 8 bits do not change.
• Seven-segment decode table is as follows.
Operation error
There is no operation error.
(s)
Seven-segment
data components
(d)
Display
data
Hexadec
imal
b3
b2
b1
b0
b15 to
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
0
0
0
1
0
0
0
0
0
0
0
0
1
1
0
2
0
0
1
0
0
0
0
0
1
0
1
1
0
1
1
3
0
0
1
1
0
0
0
0
1
0
0
1
1
1
1
4
0
1
0
0
0
0
0
0
1
1
0
0
1
1
0
5
0
1
0
1
0
0
0
0
1
1
0
1
1
0
1
6
0
1
1
0
0
0
0
0
1
1
1
1
1
0
1
7
0
1
1
1
0
0
0
0
0
1
0
0
1
1
1
8
1
0
0
0
0
0
0
0
1
1
1
1
1
1
1
9
1
0
0
1
0
0
0
0
1
1
0
1
1
1
1
A
1
0
1
0
0
0
0
0
1
1
1
0
1
1
1
B
1
0
1
1
0
0
0
0
1
1
1
1
1
0
0
C
1
1
0
0
0
0
0
0
0
1
1
1
0
0
1
D
1
1
0
1
0
0
0
0
1
0
1
1
1
1
0
E
1
1
1
0
0
0
0
0
1
1
1
1
0
0
1
F
1
1
1
1
0
0
0
0
1
1
1
0
0
0
1
b0
b1
b2
b3
b4
b5
b6
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......