758
10 BUILT-IN ETHERNET FUNCTION INSTRUCTIONS
10.4 SLMP Frame Send Instruction
■
Control data
Device
Item
Description
Setting range
Set by
(s1)+0
Execution/error
completion type
(1) Execution type (b0)
• 0: Without arrival check (The instruction is regarded as completed when a request
message is sent from own station.)
• 1: With arrival check (The instruction is regarded as completed when a response
message is received from the target device.)
(2) Error completion type (b7)
Specify whether to set data at completion with an error.
• 0: Do not set data in (s1)+13 and later at completion with an error. (Clear (s1)+13
and later.)
• 1: Set data in (s1)+13 and later at completion with an error.
User
(s1)+1
Completion status
The completion status is stored upon completion of the instruction.
0000H: Completed successfully
Other than 0000H: Completed with an error (error code)
System
(s1)+2
Channel numbers to be
used by own station
Specify the channel to be used by own station.
1: No serial number is given
1
User
(s1)+3
IP address of target
device (third and fourth
octets)
Specify the IP address (third and fourth octets) of target device.
3, 4: Indicates the octets of the IP address.
00000001H to
DFFFFFFEH
(both (s1)+3 and
(s1)+4 together)
(1 to
3758096382)
User
(s1)+4
IP address of target
device (first and second
octets)
Specify the IP address (first and second octets) of target device.
1, 2: Indicates the octets of the IP address.
User
(s1)+5
Destination port
number
Specify the destination port number.
1 to 65534
(1 to FFFEH)
User
(s1)+6
Request destination
network number
0000H (fixed)
0000H
User
(s1)+7
Request destination
station number
00FFH (fixed)
00FFH
User
(s1)+8
Request destination
module I/O number
Specify request destination module I/O number.
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: To own station (control CPU)
When executing the SP.SLMPSND instruction to FX5CPU, specify “03FFH”.
03D0H to 03D3H
03E0H to 03E3H
03FFH
User
(s1)+9
Request destination
multidrop station
number
0000H (fixed)
0000H
User
(s1)+10
Number of resends
The device becomes effective when the execution type specified by (s1)+0 is "1: With
arrival check".
■
Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+11.
• 0 to 15 (times)
■
At completion of instruction
The number of resends performed (result) is stored.
• 0 to 15 (times)
0 to 15
User/
system
(s1)+11
Arrival monitoring time
Set the monitoring time until completion of processing. If processing is not completed
within the monitoring time, the request is resent the number of times specified in
(s1)+10.
• 0: 10 s
• 1 to 32767: 1 to 32767 s
0 to 32767
User
b15
b7
b0
1
0
0
(2)
(1)
b15
b7
b8
b0
3
4
b15
b7
b8
b0
1
2
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......