12 NETWORK COMMON INSTRUCTION
12.1 Link Dedicated Instructions
769
12
■
Control data
*1 If completion status ((s1)+1) is "Channel in use (dedicated instruction) (error codes: D25AH and D25BH)", data is not stored.
Device
Item
Description
Setting range
Set by
(s1)+0
Error completion type
(1) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Do not set data in (s1)+11 and later at completion with an error.
• 1: Set data in (s1)+11 and later at completion with an error.
0000H
0080H
User
(s1)+1
Completion status
The instruction completion status is stored.
• 0: Normal
• Other than 0: Error (error code)
System
(s1)+2
Own station channel
Specify the channel to be used by own station.
1, 2
User
(s1)+3
Target station CPU type
Specify the CPU type of the target station.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
0000H
03D0H to 03D3H
03E0H to 03E3H
03FFH
User
(s1)+4
Target network number
Specify the network number (1 to 239) of the target station.
1 to 239
User
(s1)+5
Target station number
Specify the station number of the target station.
• 125: Master station
• 126: Master operating station
• 1 to 120: Local station, intelligent device station, submaster station
1 to 120, 125, 126
User
(s1)+6
Not used
(s1)+7
Number of resends
■
Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+8.
■
At completion of instruction
The number of resends performed (result) is stored.
0 to 15
User/
system
(s1)+8
Arrival monitoring time
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
0 to 32767
User
(s1)+9
Read data length
Specify the number of words to be read.
• 1 to 960 (words)
(When reading data from QnACPU: 1 to 480 (words))
1 to 960
User
(s1)+10
Not used
(s1)+11
Clock set flag
The validity status (valid or invalid) of the data in (s1)+12 and later is stored. Note
that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
• 0: Invalid
• 1: Valid
System
(s1)+12
Clock data
(Set only in an
abnormal state)
Upper 8 bits: Month (01H to 12H)
Lower 8 bits: Lower 2 digits of year (00H to 99H)
System
(s1)+13
Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
System
(s1)+14
Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
System
(s1)+15
Upper 8 bits: Upper 2 digits of the year (00H to 99H)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
System
(s1)+16
Error detection network
number
The network number of the station in which an error was detected is stored. (No
information is stored if an error is detected in the own station.)
• 1 to 239 (Network number)
System
(s1)+17
Error-detected station
number
The station number of the station where an error was detected is stored. (No
information is stored if an error is detected in the own station.)
• 125: Master station
• 1 to 120: Local station, intelligent device station, submaster station
System
b15
0
0
(1)
b7
b8
b0
…
…
b6
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......