![background image](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-f-fx5/melsec-iq-f-fx5_programming-manual_239114441.webp)
8 APPLICATION INSTRUCTION
8.8 Character String Operation Instruction
439
8
• Even though the device range of the data to be transferred (s) to (s)+n and the device range for storing the transferred data
(d) to (d)+n overlap, the processing is performed normally. For example, when a character string stored in D10 to D13 is
transferred to D11 to D14, the transfer is executed as shown below:
• When "00H" is stored in the lower byte of (s)+n, "00H" is stored to both the upper byte and lower byte of (d)+n.
Operation error
(1): It is the same as the character string before transfer.
(1): The high-order byte is not transferred.
(2): It is the same as the character string before transfer.
(3): "00H" is automatically stored in the high-order byte.
Error code
(SD0/SD8067)
Description
2820H
In the corresponding device range of the device specified by (s) and later, "00H" does not exist.
3405H
The character string specified by (s) has more than 16383 characters.
3406H
The whole specified character string cannot be stored in the devices from the device specified by (d) to the last device in the
corresponding device range.
b15
b0
D11
D10
D12
D13
D14
32H (2)
b8
31H (1)
b7
33H (3)
34H (4)
35H (5)
36H (6)
0000H
b15
b0
D11
D10
D12
D13
D14
32H (2)
b8
31H (1)
32H (2)
31H (1)
b7
33H (3)
34H (4)
35H (5)
36H (6)
0000H
(1)
b15
42H (B)
b8 b7
b0
44H (D)
41H (A)
43H (C)
00H
45H (E)
(s)
(s)+1
(s)+2
b15
b0
00H
(d)+1
(d)
(d)+2
42H (B)
b8
41H (A)
b7
43H (C)
44H (D)
00H
(2)
(1)
(3)
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......