1074
30 TIMER FUNCTION BLOCKS
30.4 Timer Function Blocks
■
TIMER_10_FB_M
• When the execution condition of (s1) turns on, counting the current value starts. The timer starts counting from "(s3)
10
ms". When it counts up to "(s2)
10 ms", (d2) turns on. The current measurement value is output into (d1).
• When the execution condition of (s1) turns off, the current value is reset to (s3) and (d2) turns off.
• A value in the range of 0 to 32767 can be specified for (s2).
• A value in the range of -32768 to 32767 can be specified for (s3). However, when a negative value is specified, the initial
value is set to 0.
Ex.
[Ladder example]
[Timing chart]
■
TIMER_100_FB_M
• When the execution condition of (s1) turns on, counting the current value starts. The timer starts counting from "(s3)
100
ms". When it counts up to "(s2)
100 ms", (d2) turns on. The current measurement value is output into (d1).
• When the execution condition of (s1) turns off, the current value is reset to (s3) and (d2) turns off.
• A value in the range of 0 to 32767 can be specified for (s2).
• A value in the range of -32768 to 32767 can be specified for (s3). However, when a negative value is specified, the initial
value is set to 0.
Ex.
[Ladder example]
[Timing chart]
Preset
ValueOut
Status
ValueIn
TIMER_10_FB_M
Coll
1
10
M0
M10
D10
OFF
OFF
M0
D10
M10
10
90 ms
ON
1
Preset
ValueOut
Status
ValueIn
TIMER_100_FB_M
Coll
1
10
M0
M10
D10
OFF
OFF
M0
D10
M10
10
90 ms
ON
1
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......