8 APPLICATION INSTRUCTION
8.8 Character String Operation Instruction
Operation error
• The value "00H" is automatically stored at the end of the converted character string.
• When the number of all digits is even, "0000H" is stored in the device after the last character. When the number of all digits is odd, "00H" is stored in the
upper byte (8 bits) of the device storing the final character.
Error code
(SD0/SD8067)
Description
3401H
The number of digits specified by (s1) is smaller than the number of digits plus 2 of the 16-bit binary data in the device specified by (s2).
(The additional 2 digits indicate the sign (+/-) and the decimal point.)
The total number of digits specified by (s1) is out of the valid range (2 to 13).
The number of digits in the decimal part specified by (s1)+1 is out of the valid range (0 to 10).
The relationship between the total number of digits specified by (s1) and the number of digits in the decimal part specified by (s1)+1 does
not satisfy the following.
(Total number of digits)-3
Number of digits in the decimal part
3406H
The device areas storing the character string specified by (d) exceed the corresponding device range.
2820H
The device range specified by (s1) exceeds the corresponding device range.
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......