320
7 BASIC INSTRUCTIONS
7.5 Data Conversion Instructions
Operation error
Error code
(SD0/SD8067)
Description
2820H
The device specified by (d1) exceeds the corresponding device range.
When "00H" is not set in the corresponding device range after the device specified in (s).
3401H
The number of characters of the character string specified by (s) is other than 2 to 8 characters.
The number of characters of the decimal part of the character string specified by (s) is other than 0 to 5 characters.
The relationship between the total number of characters specified by (s) and the number of characters of the decimal part is other than
that described below.
Total number of characters - 3
Number of characters in the decimal part
An ASCII code other than 20H, 2DH is set in the sign. (a signed value is specified)
An ASCII code other than 30H to 39H, and 2EH (decimal point) is set in the digits of each number
Two or more decimal points are set.
The converted binary value exceeds the range that can be converted by each instruction.
Signed operation: -32768 to +32767, unsigned operation: 0 to 65535