788
12 NETWORK COMMON INSTRUCTION
12.1 Link Dedicated Instructions
■
Control data
Device
Item
Description
Setting range
Set by
(s1)+0
Execution/error
completion type
(1) Execution type (bit 0)
• 0: No arrival acknowledgment
When the target station is in the same network: Completed when data has been sent
from the own station.
When the target station is in another network: Completed when data has arrived the
relay station of the own network.
• 1: Arrival acknowledgment used
Completed when data has been stored in the specified channel of the target station.
(2) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Clock data at error occurrence is not stored in (s1)+11 and later.
• 1: Clock data at error occurrence is stored in (s1)+11 and later.
0000H
0001H
0080H
0081H
User
(s1)+1
Completion status
The instruction completion status is stored.
• 0: Normal
• Other than 0: Error (error code)
System
(s1)+2
Own station channel
Specify the channel to be used by own station.
1, 2
User
(s1)+3
Target station storage
channel
Specify the channel of the target station for storing data.
1 to 8
User
(s1)+4
Target network number
Specify the network number of the target station.
• 1 to 239 (Network number)
1 to 239
User
(s1)+5
Target station number
Specify the station number of the target station.
(1) Station number specification
• 125: Master station
• 126: Master operating station
• 1 to 120: Local station, intelligent device station, submaster station
(2) Group number specification
0081H to 00A0H: All stations with group numbers 0001H to 0020H
(Can be set when the execution type specified by (s1)+0 is "0: No arrival
acknowledgment")
(3) All-station specification
00FFH: All stations of target network number (broadcast (excluding the own station))
(Can be set when the execution type specified by (s1)+0 is "0: No arrival
acknowledgment")
Station No.: 1 to
120, 125, 126
Group number
specification:
0081H to 00A0H
All-station
specification:
00FFH
User
(s1)+6
Not used
b15
0
0
(2)
(1)
b7
b0
…
…
Completed
Target
station
Request
source
Completed
Target
station
Request
source
Relay
station
Completed
Target
station
Request
source
Relay
station
Target
station
Completed
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......