8 APPLICATION INSTRUCTION
8.17 Pulse Related Instruction
611
8
Operation error
Error code
(SD0/SD8067)
Description
Axis 1
Axis 2
Axis 3
Axis 4
SD5510
SD5550
SD5590
SD5630
1810H
The axis number specified by (d) is used by another instruction.
2820H
The value specified by (s) is outside the following range.
0 to 65535
The value specified by (n) is outside the following range.
0 to 65535
The value specified by (d) is outside the following range.
0 to 3
3600H
The axis number specified by (d) is not set by parameters.
A function which is set to be not used by parameters (such as interrupt input signal 1 and zero return
relations) is used.
3631H
3632H
3633H
3634H
The numbers of pulses (by the pulses conversion) of the positioning address specified by (n) exceed the 32-
bit range.
3641H
3642H
3643H
3644H
The numbers of pulses (by the pulses conversion) of the command speed specified by (s) exceed the 32-bit
range.
3651H
3652H
3653H
3654H
The operation decelerates and stops by the forward limit or reverse limit during the pulse output or at the
activating of the positioning.
3661H
3662H
3663H
3664H
The operation decelerates and stops by the pulse output stop command or special relay whose all outputs
are disabled during the pulse output or at the activating of the positioning.
Summary of Contents for MELSEC iQ-F FX5
Page 1: ...MELSEC iQ F FX5 Programming Manual Instructions Standard Functions Function Blocks ...
Page 2: ......
Page 17: ...15 CONTENTS ...
Page 24: ...22 MEMO ...
Page 1050: ...1048 26 TIME DATA FUNCTIONS 26 4 Division MEMO ...
Page 1068: ...1066 29 COUNTER FUNCTION BLOCKS 29 4 Counter Function Block Operation error There is no error ...
Page 1107: ...I 1105 MEMO ...
Page 1111: ......