730
8 APPLICATION INSTRUCTION
8.26 Module Access Instruction
Processing details
■
TOD(P)
• These instructions write the (n) points of data in the device starting from the one specified by (s2) to the buffer memory
address specified by (s1) in intelligent function module specified by (U/H).
• When a constant is specified in (s2), (n) words of the same data (the value specified by (s2)) is written starting from the
specified buffer memory address.
■
DTOD(P)
• These instructions write the (n)
2 points of data in the device starting from the one specified by (s2) to the buffer memory
address specified by (s1) in intelligent function module specified by (U/H).
• When a constant is specified in (s2), (n)
2 words of the same data (the value specified by (s2)) is written starting from the
specified buffer memory address.
(s2)
(s1)
CPU module
Buffer memory
(n) points
(n) words
(s2)
(s1)
0
5
5
5
5
CPU module
Buffer memory
(n) words (The same data is written.)
(s2)
(s1)
(n)
2 words
(n)
2 points
CPU module
Buffer memory
(s2)
(s1)
70000
70000
70000
70000
CPU module
Buffer memory
(n)
2 words (The same data is written.)