4.4 Command Option Attachable-type FT82 SERVOPACKs with INDEXER Modules
4-128
Pn460
2
Notch Filter Adjustment
Selections 1
0000h to
0101h
–
0101h
All
Immedi-
ately
Tuning
*1
Pn475
2
Gravity Compensation-
Related Selections
0000h to
0001h
–
0000h
All
After
restart
Setup
*1
Pn476
2
Gravity Compensation
Torque
-1,000 to
1,000
0.1%
0
All
Immedi-
ately
Tuning
*1
Pn502
2
Rotation Detection Level
0 to 10,000
1 min
-1
20
Rotary
Immedi-
ately
Setup
*1
Pn503
2
Reserved parameter (Do
not change.)
–
–
10
Rotary
–
–
–
Pn506
2
Brake Reference-Servo
OFF Delay Time
0 to 50
10 ms
0
All
Immedi-
ately
Setup
*1
Pn507
2
Brake Reference Out-
put Speed Level
0 to 10,000
1 min
-1
100
Rotary
Immedi-
ately
Setup
*1
Pn508
2
Servo OFF-Brake Com-
mand Waiting Time
10 to 100
10 ms
50
All
Immedi-
ately
Setup
*1
Pn509
2
Momentary Power Inter-
ruption Hold Time
20 to 50,000
1 ms
20
All
Immedi-
ately
Setup
*1
Pn50A
2
Reserved parameter (Do
not change.)
–
–
1881h
*2
All
–
–
–
Pn50B
2
Reserved parameter (Do
not change.)
–
–
8882h
*2
All
–
–
–
Pn50E
2
Reserved parameter (Do
not change.)
–
–
0000h
*5
All
–
–
–
Pn50F
2
Reserved parameter (Do
not change.)
–
–
0100h
*6
All
–
–
–
Pn510
2
Reserved parameter (Do
not change.)
–
–
0000h
*1
All
–
–
–
Pn511
2
Reserved parameter (Do
not change.)
–
–
6543h
*7
All
–
–
–
Continued on next page.
Continued from previous page.
Parameter
No.
Size
Name
Setting
Range
Setting
Unit
Default
Setting
Applicable
Motors
When
Enabled
Classi-
fication
Refer-
ence
n.
X
Notch Filter Adjustment Selection 1
0
Do not adjust the first stage notch filter automatically during execution of auto-
tuning without a host reference, autotuning with a host reference, and custom
tuning.
1
Adjust the first stage notch filter automatically during execution of autotuning
without a host reference, autotuning with a host reference, and custom tuning.
n.
X
Reserved parameter (Do not change.)
n.
X
Notch Filter Adjustment Selection 2
0
Do not adjust the second stage notch filter automatically during execution of
autotuning without a host reference, autotuning with a host reference, and
custom tuning.
1
Adjust the second stage notch filter automatically during execution of autotun-
ing without a host reference, autotuning with a host reference, and custom
tuning.
n.X
Reserved parameter (Do not change.)
n.
X
Gravity Compensation Selection
0
Disable gravity compensation.
1
Enable gravity compensation.
n.
X
Reserved parameter (Do not change.)
n.
X
Reserved parameter (Do not change.)
n.X
Reserved parameter (Do not change.)