Fault Conditions
8 - 4
Modified: 9/17/08
MedWeld 4000 Operator’s Guide
M-032116 Proograms #T03300, #T02300 and #T02400
Control Stop
(See p. 5-2)
The control detected
that the CONTROL
STOP input (nor-
mally HIGH) dropped
out.
The CONTROL STOP input
from the robot or program
was not active when the con-
trol tried to initiate a weld.
Check/repair ladder logic. Note
if the Control Stop message is
both DIO and Serial I/O.
The external or internal wiring
(feeding CS1 and CS2) or the
input module is open, causing
a loss of input voltage to the
input.
Check the wiring to verify that
24 VDC or 120 VAC is being
provided to the CONTROL
STOP input.
The operator or ladder logic
removed the CONTROL
STOP input.
Check and correct the cause.
Stepper
Approaching
Maximum
(See p. 5-2)
The linear stepper assigned to the schedule initiated
has started the first weld in the last step.
The electrodes will soon need
maintenance. Dress or replace
the electrodes to avoid the END
OF STEPPER fault condition.
The stepper profile is programmed incorrectly.
Check the stepper profile.
End of
Stepper
(See p. 5-3)
A linear stepper in the group # assigned to the sched-
ule initiated completed the last step in the profile.
Dress or replace the electrode
tips. Reset the stepper.
Message
Explanation
Possible Cause
Remedy
Содержание MedWeld 4000
Страница 77: ...9 cdQ Y W dXU UTGU T _TYVYUT UTGU T UbQd_bµc 7eYTU b_WbQ c D D Q T D This page is intentionally left blank ...
Страница 153: ...Weld Schedules 4 54 Modified 9 17 08 MedWeld 4000 Operator s Guide M 032116 Programs T03300 T02300 and T02400 ...
Страница 255: ...Hardware Troubleshooting 9 10 Modified 9 17 08 MedWeld 4000 Operator s Guide M 032116 Programs T03300 T02300 and T02400 ...
Страница 257: ...Application Note Current Compensation 2 ML 010041 Application Note Current Compensation ...
Страница 261: ...Application Note Cascade Welding 4 ML 010041 Application Note Cascade Firing ...