Communications and I/O
MedWeld 4000 Operator’s Guide
Modified: 9/17/08
3 - 3
M-032116 Programs #T03300, #T02300 and #T02400
•
The charging pack is ready to be activated (to charge the
inverter capacitors and provide DC bus voltage).
TRANSFORMER OVER-TEMPERATURE Input
(Type 1/Type 2 inverters in FieldBus communications only):
This input tells the state of the cooling system. It is provided as an
external welding transformer over-temperature switch. If not used,
this input must be jumpered HIGH.
If this input is not active when the control receives a schedule
initiate, a SYSTEM COOLING fault will be generated and the NO
FAULT output will be de-energized.
A SYSTEM COOLING fault also occurs if a weld schedule
contains Function #79 (WAIT nnn CY FOR SYSTEM COOLING),
and this input does not become active within the number of cycles
specified.
Local Outputs
ISOLATION CONTACTOR Output ISOC
The ISOLATION CONTACTOR output operates the weld
transformer isolation contactor. Refer to page 5-5 for further
information.
SHUNT TRIP Output
Activating this output trips the circuit breaker in case of a
catastrophic failure.
Содержание MedWeld 4000
Страница 77: ...9 cdQ Y W dXU UTGU T _TYVYUT UTGU T UbQd_bµc 7eYTU b_WbQ c D D Q T D This page is intentionally left blank ...
Страница 153: ...Weld Schedules 4 54 Modified 9 17 08 MedWeld 4000 Operator s Guide M 032116 Programs T03300 T02300 and T02400 ...
Страница 255: ...Hardware Troubleshooting 9 10 Modified 9 17 08 MedWeld 4000 Operator s Guide M 032116 Programs T03300 T02300 and T02400 ...
Страница 257: ...Application Note Current Compensation 2 ML 010041 Application Note Current Compensation ...
Страница 261: ...Application Note Cascade Welding 4 ML 010041 Application Note Cascade Firing ...