Advanced Software Features
MedWeld 4000 Operator’s Guide
Modified: 9/17/08
7 - 19
M-032116 Programs #T03300, #T02300 and #T02400
The example schedule shown above provides the following:
•
The first function (#82) assigns the schedule to the proper stepper
profile.
•
The second function is used to prevent the control from executing a
weld schedule while the gun is in the full retract position. If the gun
is not in the partial retract position, the control will generate the
RETRACT PILOT fault as a result of Function #80.)
NOTE:
Program the
RETRACT PILOT
fault as an
ALERT
condition in the
setup parameters, so that the operator can place the valve in the partial
retract position and re-initiate the weld schedule.
If this condition is defined as a
FAULT
, the control will require a fault
reset before it can continue. (An exception is when the
Initiation On Fault
setup parameter is set to
ALLOW
, as described on page 5-10.)
•
If the weld schedule does NOT contain this function, the control
lets you execute a sequence with the gun in the full retract position.
If firing the control from full retract, the Extend Sqz From Retract
(CY/2) setup parameter is added to the time the gun is closed under
only hydraulic pressure.
NOTE:
These functions are enabled
ONLY
when setting the
Cylinder Type
setup
parameter to
AIR-OVER-OIL
. The outputs controlling the Advance,
Intensify and Blocking valves do
NOT
turn on when the air-only
cylinders are selected.
•
The TURN ON ADVANCE VALVE function contains the time the
gun will close under hydraulic pressure: (20 cycles in this
example).
•
The function TURN ON INTENSIFY VALVE contains the time the
gun will close and build up pressure under air pressure: (10 cycles
in our example).
•
The next two functions define the weld and hold time.
•
Finally, the control turns off the Advance and Intensify valves for
the time set in the setup parameter Blocking Valve #n Delay (CY/
2). When firing the control from the full retract position, the setup
parameter Extend Sqz From Retract (CY/2) value is added to the
value of Blocking Valve #n Delay. This allows the gun to return to
the prior position.
Содержание MedWeld 4000
Страница 77: ...9 cdQ Y W dXU UTGU T _TYVYUT UTGU T UbQd_bµc 7eYTU b_WbQ c D D Q T D This page is intentionally left blank ...
Страница 153: ...Weld Schedules 4 54 Modified 9 17 08 MedWeld 4000 Operator s Guide M 032116 Programs T03300 T02300 and T02400 ...
Страница 255: ...Hardware Troubleshooting 9 10 Modified 9 17 08 MedWeld 4000 Operator s Guide M 032116 Programs T03300 T02300 and T02400 ...
Страница 257: ...Application Note Current Compensation 2 ML 010041 Application Note Current Compensation ...
Страница 261: ...Application Note Cascade Welding 4 ML 010041 Application Note Cascade Firing ...