7PG2113/4/5/6 Commissioning & Maintenance
©2012 Siemens Protection Devices Limited
Chapter 6 Page 58 of 77
2.16
Neutral Overvoltage (59N)
Figure 2.16-1 Neutral Overvoltage
Voltage Inputs:
V
L1
(V
A
), V
L2
(V
B
), V
L3
(V
C
)
Current Inputs:
n/a apply zero current to stabilize other functions
Disable:
27/59,
47,
60VTS
Map Pickup LED:
59N-n - Self Reset
The voltage source for the Neutral Overvoltage 59N function can be set as either Vn , calculated from the applied
3 phase voltage inputs or Vx, the V
4
input. Apply test voltage to 1 phase input or V
4
input to suit.
2.16.1 Definite Time (59NDT)
If DTL setting is small, gradually increase single phase voltage until element operates.
If DTL is large apply 0.9x setting, check for no operation, apply 1.1x setting, check operation
Apply 2x setting voltage if possible and record operating time
Phase Vs
(Volts)
DTL
(sec)
P.U. Current
Volts
Operate Time
2 x Vs
Tolerence
E
Table 2.16-1
59NDT Test Results
Check correct indication, trip output, alarm contacts, waveform record.