OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes (dec)
Qualifier Codes
(hex)
Function
Codes (dec)
Qualifier
Codes (hex)
11 2
Binary Output Change with
Time
1 (read)
06 (no range,
or all)
07, 08 (limited
qty)
129
(response)
130
(unsol. resp)
17, 28 (index )
12
0
Control Relay Output Block
22
(assign
class)
00, 01
(start-stop)
06 (no range,
or all)
07, 08 (limited
qty)
17, 27,
28(index)
12
1
Control Relay Output Block 3
(select)
4 (operate)
5 (direct op)
6 (dir.
op,
noack)
17, 28 (index) 129
(response)
echo of
request
12
2
Pattern Control Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op,
noack)
7 (limited
quantity)
129
(response)
echo of
request
12 3
Pattern
Mask
3 (select)
4 (operate)
5 (direct op)
6 (dir. op,
noack)
00, 01
(start-stop)
129
(response)
echo of
request
30
0
Analog Input - Any Variation 1 (read)
22
(assign
class)
00, 01
(start-stop)
06 (no range,
or all)
07, 08
(limited qty)
17, 27,
28(index)