7PG2113/4/5/6 Data Communications
©2010 Siemens Protection Devices Limited
Chapter 4 Page 26 of 38
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Number
Description
Function
Codes (dec)
Qualifier Codes
(hex)
Function
Codes (dec)
Qualifier
Codes (hex)
30
1
32-Bit Analog Input
1 (read)
00, 01
(start-stop)
06 (no range,
or all)
07, 08
(limited qty)
17, 27,
28(index)
129
(response)
00, 01(start-sto
17, 28(index –
see note 2)
30 2
16-Bit Analog Input
1 (read)
00, 01
(start-stop)
06 (no range,
or all)
07, 08 (limited
qty)
17, 27,
28(index)
129(response00, 01(start-sto
17, 28(index –
see note 2)
30 3
(default
–
see note
1)
32-Bit Analog Input without
Flag
1 (read)
00, 01
(start-stop)
06 (no range,
or all)
07, 08 (limited
qty)
17, 27, 28
(index)
129(response00, 01(start-sto
17, 28(index –
see note 2)
30
4
16-Bit Analog Input without
Flag
1 (read)
00, 01
(start-stop)
06 (no range,
or all)
07, 08 (limited
qty)
17, 27,
28(index)
129
(response)
00, 01(start-sto
17, 28(index –
see note 2)
30
5
short floating point
1 (read)
00, 01
(start-stop)
06 (no range,
or all)
07, 08 (limited
qty)
17, 27,
28(index)
129
(response)
00, 01
(start-stop)
17, 28(index –
see
note
2)