7PG2113/4/5/6 Solkor Description of Operation
•
At the end of the
79 Reclose Blocked Delay
due to presence of a persistent Block signal.
•
When
the
79 Elem HS Trips to Lockout
count is reached.
•
When
the
79 Elem Delayed Trips to Lockout
count is reached.
Once lockout has occurred, an alarm (
79 Lockout
) is issued and all further Close commands, except manual
close, are inhibited.
If the Lockout command is received while a Manual Close operation is in progress, the feature is immediately
locked-out.
Once the Lockout condition has been reached, it will be maintained until reset. The following will reset lockout: -
•
By a Manual Close command, from fascia, comms or
Close CB
binary input.
•
By
a
79 Reset Lockout
binary input, provided there is no signal present that will cause Lockout.
•
At the end of the
79 Minimum LO Delay
time setting if
79 Reset LO by Timer
is selected to
ENABLED
, provided there is no signal present which will cause Lockout.
•
Where Lockout was entered by an A/R Out signal during an Autoreclose sequence then a
79 In
signal must be received before Lockout can reset.
•
By
the
CB Closed
binary input, provided there is no signal present which will cause Lockout.
The Lockout condition has a delayed drop-off of 2s. The Lockout condition can not be reset if there is an active
lockout input.
©2010 Siemens Protection Devices Limited Chapter 1 Page 62 of 80