7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 15 of 42
Section 2:
Protection Functions
2.1
27/59 Under/over voltage
2.1.1 Reference
Parameter
Value
V
s
Setting 5,
5.5…200V
hyst
Hysteresis setting
0, 0.1… 80.0%
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.1.2 Operate and Reset Level
Attribute
Value
V
op
Operate level
100 %
Vs
,
±
1 % or
±
0.25V
Overvoltage
= (100 % -
hyst
)
x
V
op,
±
1 % ± 0.25V
Reset level
Undervoltage
= (100 % +
hyst
)
x
V
op
±
1 % ± 0.25V
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
2.1.3 Operate and Reset Time
Attribute
Value
0 to 1.1 x
Vs
:
73 ms
±
10ms
Overvoltage
0 to 2.0 x
Vs
: 63 ms
±
10ms
t
basicE
Element basic
operate time
Undervoltage
1.1 to 0.5 x
Vs
: 58 ms
±
10ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
10ms
Repeatability
±
1 % or
±
10ms
Disengaging time
< 80 ms
2.2
37 Undercurrent
2.2.1 Reference
Parameter
Value
Is
Setting 0.05,
0.10…5.0
xIn
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.2.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
,
±
5 % or
±
1%
In
Reset level
≤
105 %
I
op
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %