7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 11 of 42
1.4.2 Line Charging Current
Maximum Primary Line Capacitive Charging Current:
Solidly Earthed System, 1/3 times the most sensitive earth fault setting
Resistance Earthed System, 1/9 times the most sensitive earth fault setting
1.5
Environmental Performance
1.5.1 General
1.5.1.1
Temperature
IEC 60068-2-1/2
Type Level
Operating range
-10
°
C to +55
°
C
Storage range
-25
°
C to +70
°
C
1.5.1.2
Humidity
IEC 60068-2-78
Type Level
Operational test
56 days at 40
°
C and 93 % relative humidity
1.5.1.3
Transient Overvoltage
IEC 60255-5
Type Level
Between all terminals and earth, or
between any two independent circuits
5.0 kV, 1.2/50
μ
s 0.5j
1.5.1.4
Insulation
IEC 60255-5
Type Level
Between any terminal and earth
Between independent circuits
2.5 kV AC RMS for 1 min
Across normally open contacts
1.0 kV AC RMS for 1 min
Between pilot circuit and all other independent
circuits and earth
5.0 kV AC RMS for 1 min
1.5.1.5
IP Ratings
IEC60529
Type Level
Installed with cover on
IP 5X, Category 2- Dust-protected
Installed with cover off
IP 4X, 1mm probe
Solkor R/Rf
Type Level
Installed with cover on
IP 51
Installed with cover removed
IP 30