7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 13 of 42
Type Level
Variation
Contact discharge
8.0 kV
≤
5 %
1.5.3.4
Radiated Immunity
IEC 60255-22-3
Type Level
80 MHz to 1000 MHz Sweep
10 V/m
1.4GHz to 2.7GHz Sweep
10V/m
80,160,380,450,900,1850,2150 MHz Spot
10V/m
1.5.3.5
Fast Transients
IEC 60255-22-4 (2002) Class A
Type Level
5/50 ns 2.5 kHz repetitive
4kV
1.5.3.6
Surge Immunity
IEC 60255-22-5
Type Level
Between all terminals and earth
0.5, 1.0, 2.0, 4.0 kV
Between Line to Line
0.5, 1.0, 2.0 kV
1.5.3.7
Conducted Radio Frequency Interference
IEC 60255-22-6
Type Level
0.15 to 80 MHz
10 V
1.5.3.8
Magnetic Field with Power Frequency
IEC 6100-4-8 Level 5
100A/m, (0.126mT) continuous
1000A/m, (1.26mT) for 3s
50Hz
1.5.4 Mechanical
1.5.4.1
Vibration (Sinusoidal)
IEC 60255-21-1 Class I
Type Level
Variation
Vibration response
0.5 gn
Vibration endurance
1.0 gn
≤
5 %
1.5.4.2
Shock and Bump
IEC 60255-21-2 Class I
Type Level
Variation
Shock response
5 gn, 11 ms
Shock withstand
15 gn, 11 ms
Bump test
10 gn, 16 ms
≤
5 %
1.5.4.3
Seismic
IEC 60255-21-3 Class I
Type Level
Variation
Seismic response
X-plane - 3.5mm displacement below crossover freq
(8-9Hz) 1.0gn above
≤
5 %