7PG2113/4/5/6 Solkor Description of Operation
2.3
Front Cover
As standard the relay is supplied with a transparent front cover. The front cover is used to secure the relay
modules in the case.
Figure 2.3-1 Relay with standard transparent cover
2.4
Power Supply Unit (PSU)
The relay can be ordered with two different nominal power supply ranges, 24V to 60V and 80V to 320V dc. The
Solkor R/Rf module does not require an auxiliary supply and is universal for all DC ratings.
In the event of the supply voltage level falling below the relay minimum operate level the PSU will automatically
switch itself off and latch out – this prevents any PSU overload conditions occurring. The PSU is reset by
switching the auxiliary supply off and on.
2.5
Operator Interface/ Fascia
The operator interface is designed to provide a user-friendly method of controlling, entering settings and retrieving
data from the relay. Links are provided to allow setting of pilot padding resistance and test points are provided to
allow operating spill current to be measured.
Figure 2.5-1 Relay with Transparent cover removed
©2010 Siemens Protection Devices Limited Chapter 1 Page 17 of 80