7PG2113/4/5/6 Solkor Description of Operation
4.1.2 Instantaneous Overcurrent Protection (50)
Two Instantaneous overcurrent elements are provided in the 7PG2113/5 relay and four elements are provided in
the 7PG2114/6 relay.
50-1, 50-2, (50-3 & 50-4 – 7PG2114/6)
Each instantaneous element (50-n) has independent settings.
50-n Setting
for pick-up current and
50-n Delay
follower time delay. The instantaneous elements have transient free operation.
Where directional elements are present the direction of operation can be set using
50-n Dir. Control
setting.
Directional logic is provided independently for each 50-n element, e.g. giving the option of using two elements set
to forward and two to reverse.
Operation of the instantaneous overcurrent elements can be inhibited from:
Inhibit 50-n
A binary or virtual input.
79 P/F Inst Trips: 50-n
When ‘delayed’ trips only are allowed in the auto-reclose sequence
(
79 P/F Prot’n Trip n
=
Delayed
).
50-n Inrush Action: Block
Operation of the inrush current detector function.
50-n VTS Action: Inhibit
Operation of the VT Supervision function (7PG2114/6).
Figure 4.1-2 Logic Diagram: Instantaneous Over-current Element
©2010 Siemens Protection Devices Limited Chapter 1 Page 37 of 80