7PG2113/4/5/6 Data Communications
©2010 Siemens Protection Devices Limited
Chapter 4 Page 30 of 38
5.3
Point List
The tables below identify all the default data points provided by the implementation of the Triangle MicroWorks,
Inc. DNP 3.0 Slave Source Code Library.
The default binary input event buffer size is set to allow 100 events.
Note, not all points listed here apply to all builds of devices.
Binary Input Points
Static (Steady-State) Object Number:
1
Change Event Object Number:
2
Default Static Variation reported when variation 0 requested:
2 (Binary Input with flags)
Default Change Event Variation reported when variation 0 requested:
2 (Binary Input with absolute time)
Point
Index
Name/Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
1
Binary Input 1
2
2
Binary Input 2
2
3
Binary Input 3
2
4
Binary Input 4
2
5
Binary Input 5
2
6
Binary Input 6
2
35 Remote
mode
2
36 Service
mode
2
37 Local
mode
2
38
Local & Remote
2
41
Trip Circuit Fail
2
42 A-Starter
2
43 B-Starter
2
44 C-Starter
2
45 General
Starter
2
46 VTS
Alarm
2
47
Earth Fault Forward/Line
2
48
Earth Fault Reverse/Busbar
2
49 Start/Pick-up
N
2
50 Fault
Forward/Line
2
51 Fault
Reverse/Busbar
2
52 51-1
2
53 50-1
2
56 51G-1
2
57 50G-1
2
58 51-2
2
59 50-2
2
60 51N-2
2
61 50N-2
2