7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 33 of 42
2.13 59N Neutral Voltage Displacement
2.13.1 Reference (59NDT)
Parameter
Value
Vs
Setting
0.1 x Vn
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010… 10000,
10100… 14400 s
2.13.2 Operate and Reset Level (59NDT)
Attribute
Value
V
op
Operate level
100 %
Vs
,
±
2 % or
±
0.5 V
Reset level
≥
95 %
V
op
or
±
0.5 V
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %
2.13.3 Operate and Reset Time (59NDT)
Attribute
Value
0V to 1.5
xVs
, 76 ms,
±
20ms
t
basic
Element basic operate time
0V to 10
xVs
, 63 ms,
±
20ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
1 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Overshoot time
< 40 ms
Disengaging time
<100 ms
2.13.4 Reference (59NIT)
Parameter
Value
M
Multiplier setting
1
Vs
Setting
1, 1.5… 100V
3V
o
Applied Current (for Operate-Time)
IDMTL
2 x Vs
t
d
Delay setting
0, 0.01… 20 s
t
res
Reset setting
0, 1…60 s
2.13.5 Operate and Reset Level (59NIT)
Attribute
Value
V
op
Operate level
105 %
Vs
,
±
2 % or
±
0.5 V
Reset level
≥
95 %
V
op
or
±
0.5 V
Repeatability
±
1 %
-10 °C to +55 °C
≤
5 %
Variation
f
nom
- 3 Hz to
f
nom
+ 2 Hz
≤
5 %