7PG2113/4/5/6 Commissioning & Maintenance
©2012 Siemens Protection Devices Limited
Chapter 6 Page 64 of 77
3.3
Current Transformer Supervision (60CTS)
3.3.1 7PG2113
&
7PG2115
Figure 3.3-1 Current Transformer Supervision 7PG2113/5
Current Inputs:
I
L1
(I
A
), I
L2
(I
B
), I
L3
(I
C
)
Disable:
51N, 46IT, 46DT, 46BC
Map Pickup LED:
60CTS - Self Reset
Apply 3Phase balanced current to the relay, reduce the current in any one or two phases to a level below
60CTS I
setting. Measure the delay to operation.
Gradually reduce the 3Phase current until the element resets.
Setting Measured
60CTS Delay
60CTS Inps
60CTS Vnps
Table 3.3-1
7SR11 60CTS Test Results