7PG2113/4/5/6 Performance Specification
©2010 Siemens Protection Devices Limited
Chapter 3 Page 37 of 42
If Pilot Supervision is fitted, the settings will be increased by 20-50%.
In Rf mode the remote end relay will operate at a similar level to the local relay.
In R mode the remote end will typically operate at 2.5 times the local end setting.
2.16.2 Operate Time
Attribute
Mode
3x fault setting
5x fault setting
10x fault setting
R Mode
60ms
45ms
5kV Rf mode
45ms
t
RfBasic
Element typical basic
operate time
15kV Rf mode
40ms
2.16.3 Stability Level
Parameter
Value
I
StabLimit
Maximum Through fault Stability Level
50x In
Fault settings (% In)
Without isolating transformers
With isolating transformers
R Mode
Rf Mode
R Mode
Rf Mode
Type of
fault
N1 tap
N tap
N1 tap
N tap
N1 tap
N tap
N1 tap
N tap
a-n 16 22 18 25 22 31 25
35
b-n 18
27.5 21 32 26 39 30
44
c-n 22 37 25 42 31 52 35
59
a-b 110
125
155
177
b-c 110
125
155
177
c-a 55
62
77.5
88.5
a-b-c 63
72
89
101