7PG2113/4/5/6 Commissioning & Maintenance
©2012 Siemens Protection Devices Limited
Chapter 6 Page 37 of 77
2.8
Measured Earth fault (67/50G,67/51G)
Figure 2.8-1 Measured Earth Fault
Voltage Inputs:
V
L1
(V
A
), V
L2
(V
B
), V
L3
(V
C
) for directional elements
Current Inputs:
I
4
(I
G
)
Disable:
50CBF,
79
Map Pickup LED:
51G-n/50G-n - Self Reset
Other protection functions may overlap with these functions during testing, it may be useful to disable some
functions to avoid ambiguity. Derived EF, Measured EF, Sensitive EF & Restricted EF protections can be
Enabled/Disabled individually or as groups in the ‘Function Config’ menu.
Measured EF elements can be separated from Derived EF and Sensitive EF by secondary injection of current
through the I
4
input circuit only.
If any of these elements are defined as directional the correct voltage phase direction will be required to produce
an operation of those elements.