7PG2113/4/5/6 Commissioning & Maintenance
©2012 Siemens Protection Devices Limited
Chapter 6 Page 51 of 77
2.12.1.1 Element
Blocking
The Undercurrent elements can be blocked by Binary Input Inhibit. This functionality should be checked.
Element BI
Inhibits
37-1
37-2
Table 2.12-2
Element Blocking
Check correct indication, trip output, alarm contacts, waveform record.