![Siemens Solkor 7PG2113 Скачать руководство пользователя страница 166](http://html.mh-extra.com/html/siemens/solkor-7pg2113/solkor-7pg2113_technical-manual_382683166.webp)
7PG2113/4/5/6 Data Communications
©2010 Siemens Protection Devices Limited
Chapter 4 Page 21 of 38
DNP V3.0
DEVICE PROFILE DOCUMENT
(Also see the DNP 3.0 Implementation Table Section 5.2.)
Timeouts while waiting for:
Data Link Confirm:
None
7
Fixed at 2sec
Variable
Configurable
.
Complete Appl. Fragment:
7
None
Fixed at ____
Variable
Configurable
Application Confirm:
None
7
Fixed at 10sec
Variable
Configurable
.
Complete Appl. Response:
7
None
Fixed at ____
Variable
Configurable
Others:
Transmission Delay, (0 sec)
Select/Operate Arm Timeout, (5 sec)
Need Time Interval, (30 minutes)
Application File Timeout, (60 sec)
Unsolicited Notification Delay, (5 seconds)
Unsolicited Response Retry Delay, (between 3 – 9 seconds)
Unsolicited Offline Interval, (30 seconds)
Binary Change Event Scan Period, (Polled, Not Applicable)
Double Bit Change Event Scan Period, (Unsupported - Not Applicable)
Analog Change Event Scan Period, (Unsupported - Not Applicable)
Counter Change Event Scan Period, (Unsupported - Not Applicable)
Frozen Counter Change Event Scan Period, (Unsupported - Not Applicable)
String Change Event Scan Period, (Unsupported - Not Applicable)
Virtual Terminal Event Scan Period, (Unsupported - Not Applicable)
Sends/Executes Control Operations:
WRITE Binary Outputs
7
Never
Always
Sometimes
Configurable
SELECT/OPERATE
Never
7
Always
Sometimes
Configurable
DIRECT OPERATE
Never
7
Always
Sometimes
Configurable
DIRECT OPERATE – NO ACK
Never
7
Always
Sometimes
Configurable
Count > 1
7
Never
Always
Sometimes
Configurable
Pulse
On
Never
Always
7
Sometimes
Configurable
Pulse Off
Never
Always
7
Sometimes
Configurable
Latch
On
Never
Always
7
Sometimes
Configurable
Latch
Off
Never
Always
7
Sometimes
Configurable
Queue
7
Never
Always
Sometimes
Configurable
Clear
Queue
7
Never
Always
Sometimes
Configurable
Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.
Reports Binary Input Change Events when no
specific variation requested:
Never
Only time-tagged
Only
non-time-tagged
7
Configurable to send one or the
other
Reports time-tagged Binary Input Change Events when
no specific variation requested:
Never
Binary Input Change With Time
Binary Input Change With Relative Time
7
Configurable
Sends Unsolicited Responses:
Never
7
Configurable
Only certain objects
Sometimes (attach explanation)
7
ENABLE/DISABLE UNSOLICITED
Function codes supported
Sends Static Data in Unsolicited Responses:
7
Never
When
Device
Restarts
When Status Flags Change
No other options are permitted.
Default Counter Object/Variation:
7
No Counters Reported
Configurable
Default Object
Default Variation:
Point-by-point list attached
Counters Roll Over at:
7
No Counters Reported
Configurable (attach explanation)
16
Bits
32
Bits
Other Value: _____
Point-by-point list attached