2 Functions
68
7UT613/63x Manual
C53000-G1176-C160-2
For the winding assigned to side 3, the following data are relevant:
• Address
331
UN-PRI SIDE 3
the primary rated voltage (consider regulating
range),
• Address
332
SN SIDE 3
the primary rated apparent power,
• Address
333
STARPNT SIDE 3
the starpoint treatment,
• Address
334
CONNECTION S3
the winding connection mode,
• Address
335
VECTOR GRP S3
the vector group numeral.
For the winding assigned to side 4, the following data are relevant:
• Address
341
UN-PRI SIDE 4
the primary rated voltage (consider regulating
range),
• Address
342
SN SIDE 4
the primary rated apparent power,
• Address
343
STARPNT SIDE 4
the starpoint conditioning,
• Address
344
CONNECTION S4
the winding connection mode,
• Address
345
VECTOR GRP S4
the vector group numeral.
For the winding assigned to side 5, the following data are relevant:
• Address
351
UN-PRI SIDE 5
the primary rated voltage (consider regulating
range),
• Address
352
SN SIDE 5
the primary rated apparent power,
• Address
353
STARPNT SIDE 5
the starpoint conditioning,
• Address
354
CONNECTION S5
the winding connection mode,
• Address
355
VECTOR GRP S5
the vector group numeral.
The device automatically computes from these data of the protected transformer and
its windings the current-matching formulae which are required to match the vector
group and the different rated winding currents. The currents are converted such that
the sensitivity of the protection always refers to the power rating of the transformer.
In case of different rating of the windings, the rated apparent power of the most pow-
erful winding is the rated apparent power of the transformer. In general, no circuits are
required for matching of the vector group and no manual calculations for converting of
rated current are normally necessary.
Object Data with
Generators, Motors
and Reactors
Using the 7UT613/63x for protection of generators or motors, the following must have
been set when configuring the scope of functions (see section Functional Scope,
address
105
):
PROT. OBJECT
=
Generator/Motor
. These settings also apply for
series and shunt reactors if a complete set of current transformers is connected to both
sides. In cases other than that, these settings are not available.
With address
361
UN GEN/MOTOR
you inform the device of the primary rated voltage
(phase-to-phase) of the machine to be protected.
The primary rated power set under address
362
SN GEN/MOTOR
is the direct primary
rated apparent power of the machine. The power must always be entered as a primary
value, even if the device is generally configured in secondary values. The device cal-
culates the rated current of the protected object and its sides from this power and the
rated voltage. This is the reference for all referred values.
Object Data with
Mini-Busbars,
Branch-Points,
Short Lines (3-
phase)
These data are only required if the device is used as 3-phase differential protection for
mini busbars or short lines. When configuring the scope of functions (see Scope of
Functions, address
105
), the following must have been set:
PROT. OBJECT
=
3ph
Busbar
. In cases other than that, these settings are not available.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...