2 Functions
266
7UT613/63x Manual
C53000-G1176-C160-2
The following example illustrates a setting of the frequency protection for a generator
that indicates a delayed warning at approx. 1 % decreased frequency. In case of a
further frequency decrease, the generator is disconnected from the network and finally
shut down.
Minimum Voltage
The frequency protection is blocked on undershooting the minimum voltage
U MIN
.
The recommended value is approx. 65 % U
N
. The setting value is based on phase-
phase voltages. If the frequency protection of one side of the main protected object,
the value must be set as reference value under address
5652
U MIN
, e.g. 0.65. When
assigned to a measuring location the value of phase-phase voltage must be set under
address
5651
Umin
in Volt , e.g. 71. V at U
N sec
= 110 V (65 % of 110 V). The
minimum voltage threshold can be deactivated by setting this address to 0. However,
no frequency measuring is possible below approx. 5 V (secondary) so that the fre-
quency protection can no longer function.
2.16.3 Settings
Level
Changes to
CPU modules
Setting at f
N
=
Delay
50 Hz
60 Hz
16.7 Hz
f<
Warning
49.50 Hz
59.50 Hz
16.60 Hz
20.00 s
f<<
Disconnection
from the network
48.00 Hz
58.00 Hz
16.00 Hz
1.00 s
f<<<
Shutdown
47.00 Hz
57.00 Hz
15.70 Hz
6.00 s
f>
Warning and trip
52.00 Hz
62.00 Hz
17.40 Hz
10.00 s
Addr.
Parameter
Setting Options
Default Setting
Comments
5601
O/U FREQUENCY
OFF
ON
Block relay
OFF
Over / Under Frequency Protec-
tion
5611
f<
40.00 .. 49.99 Hz; 0
49.50 Hz
Pick-up frequency f<
5612
f<<
40.00 .. 49.99 Hz; 0
48.00 Hz
Pick-up frequency f<<
5613
f<<<
40.00 .. 49.99 Hz; 0
47.00 Hz
Pick-up frequency f<<<
5614
f>
50.01 .. 66.00 Hz;
∞
52.00 Hz
Pick-up frequency f>
5621
f<
50.00 .. 59.99 Hz; 0
59.50 Hz
Pick-up frequency f<
5622
f<<
50.00 .. 59.99 Hz; 0
58.00 Hz
Pick-up frequency f<<
5623
f<<<
50.00 .. 59.99 Hz; 0
57.00 Hz
Pick-up frequency f<<<
5624
f>
60.01 .. 66.00 Hz;
∞
62.00 Hz
Pick-up frequency f>
5631
f<
10.00 .. 16.69 Hz; 0
16.50 Hz
Pick-up frequency f<
5632
f<<
10.00 .. 16.69 Hz; 0
16.00 Hz
Pick-up frequency f<<
5633
f<<<
10.00 .. 16.69 Hz; 0
15.70 Hz
Pick-up frequency f<<<
5634
f>
16.67 .. 22.00 Hz;
∞
17.40 Hz
Pick-up frequency f>
5641
T f<
0.00 .. 100.00 sec;
∞
20.00 sec
Delay time T f<
5642
T f<<
0.00 .. 600.00 sec;
∞
1.00 sec
Delay time T f<<
5643
T f<<<
0.00 .. 100.00 sec;
∞
6.00 sec
Delay time T f<<<
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...