2.5 Time Overcurrent Protection for Earth Current
187
7UT613/63x Manual
C53000-G1176-C160-2
Since this stage also picks up with earth faults in the network, the time delay (address
2423
D IEp
) has to be coordinated with the grading coordination chart of the network
for earth faults. In most cases, shorter tripping times than for phase currents may be
set since a galvanic separation of the zero sequence systems of the connected power
system sections is ensured by a transformer with separate windings.
The time multiplier can also be set to
∞
. If set to infinity, the pickup of this function will
be indicated but the stage will not trip after pickup. If stage
IEp
is not required at all,
select address
124
DMT/IDMT Earth
=
Definite Time
during configuration of the
protection functions.
If at address
2424
TOC DROP-OUT
the
Disk Emulation
is set, dropout is thus pro-
duced in accordance with the dropout characteristic, as described under margin head-
ing„ Dropout Behaviour“ in subsection 2.5.
Dynamic Cold Load
Pickup
An alternative set of pickup values can be set for each stage. It may be selected au-
tomatically in a dynamic manner during operation. For more information on this func-
tion, see Section 2.6. For the stages the following alternative values are set here.
for definite time overcurrent protection
I
E
:
• address
2511
for pickup value
IE>>
,
• address
2512
for delay time
T IE>>
,
• address
2513
for pickup value
IE>
,
• address
2514
for delay time
T IE>
,
for inverse time overcurrent protection
I
E
acc. to IEC characteristics:
• address
2521
for pickup value
IEp
,
• address
2522
for time multiplier
T IEp
;
for inverse time overcurrent protection
I
E
acc. to ANSI characteristics:
• address
2521
for pickup value
IEp
,
• address
2523
for time multiplier
D IEp
;
User-Defined
Curves
For inverse time overcurrent protection the user may define his own tripping and
dropout characteristic. For configuration in DIGSI a dialogue box appears. Enter up to
20 pairs of current value and tripping time value.
The procedure is the same as for phase current stages. See subsection 2.4.2 under
margin heading „User-Defined Curves“.
To create a user defined tripping characteristic for earth current, the following has to
be set for configuration of the functional scope: address
124
DMT/IDMT Earth
,
option
User Defined PU
. If you also want to specify the dropout characteristic, set
option
User def. Reset
.
Inrush Restraint
In address
2402
InRushRestEarth
of the general settings, the inrush restraint can
be enabled (
ON
) or disabled (
OFF
). This inrush restraint is only sensible for transform-
ers and if overcurrent time protection is activated on the earthed feeding side. Func-
tion parameters of the inrush restraint are set in „Inrush“.
The inrush restraint is based on the evaluation of the 2nd harmonic present in the
inrush current. The ratio of 2nd harmonics to the fundamental component
2.HARM.
Earth
(address
2441
) is set to
I
2
fN
/
I
fN
=
15
% as default setting. It can be used
without being changed. To provide more restraint in exceptional cases, where ener-
gising conditions are particularly unfavourable, a smaller value can be set in the afore-
mentioned address.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...