7UT613/63x Manual
C53000-G1176-C160-2
Implementation of
Zero Sequence
Current Tests
For these commissioning tests, the zero sequence current must be at least 2 % of the
rated relay current for each phase, i.e. the test current at least 6 %.
This test cannot replace visual inspection of the correct current transformer connec-
tions. Therefore, the inspection of these connections is a prerequisite.
• Switch on test current.
• Read out the current magnitudes:
Compare the indicated current magnitudes under
measurement
→
secondary
→
operational measured values secondary
with the actually flowing values:
– All phase currents of the tested measuring location correspond to approximately
1
/
3
of the test current (for 1-phase transformers
1
/
2
),
– 3
I
0 of the tested measuring location corresponds to the test current.
– Phase currents and zero sequence current of the other measuring location are,
on transformers, nearly 0.
– The current at the auxiliary 1-phase current input corresponds to the test current
— provided this current is available and included.
Deviation can practically occur only for the single-phase current (if included)
because the connection of the phase currents had been verified already during the
symmetrical tests. In case of deviations:
– Switch off the test source and the protected object (shut down the generator) and
earth it.
– Re-check the assignment or the tested 1-phase input (subsection 2.1.4 under
margin heading „Assignment of Auxiliary 1-phase Measuring Locations“).
– Re-check the settings for the magnitude matching (Subsection 2.1.4 under
margin heading „Current Transformer Data for 1-phase Auxiliary Current In-
puts“).
– Check the plant connections to the device and the test arrangement and correct
them.
– Repeat test and re-check the current magnitudes.
Measuring Differen-
tial and Restraint
Currents
The differential and restraint currents are referred to the rated currents of the tested
side of the main protected object. If a zero sequence current test does not concern the
main protected object but a different earthed object (e.g. a shunt reactor outside the
main object), the base of the referred currents is the rated current of that 3-phase mea-
suring location to which the 1-phase current input is assigned, i.e. the measuring lo-
cation under test. This must be considered when they are compared with the test cur-
rents.
• Switch on test current.
• If the starpoint current is available:
Read out the differential and restraint currents
I-Diff
;
I-Rest
under
Measurement
→
Percent Values
→
Differential and Restraint Currents
.
– The differential current of the restricted earth fault protection
I
Diff REF
must be low,
at least one scale less than the test current.
– The stabilisaing current
I
Rest REF
corresponds to twice the test current.
Содержание SIPROTEC 7UT613 series
Страница 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Страница 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Страница 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Страница 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Страница 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Страница 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Страница 516: ...A Appendix 516 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B Figure A 7 General diagram 7UT633 panel surface mounting ...
Страница 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Страница 518: ...A Appendix 518 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N Figure A 8 General diagram 7UT633 panel surface mounting ...
Страница 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Страница 520: ...A Appendix 520 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B Figure A 9 General diagram 7UT635 panel surface mounting ...
Страница 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Страница 522: ...A Appendix 522 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N Figure A 10 General diagram 7UT635 panel surface mounting ...
Страница 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Страница 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...