Axis and Spindle Test Run
13
13.1
Requirements
Enabling signals must be set to allow an axis to be traversed directly from the control:
●
Drive: Parameters and terminals
●
NC: Interface signals
13.1.1
Drives: SINAMICS S120
Relevant parameters/terminals
Infeed
Parameter/Terminal
Description
p0840
ON/OFF1
p0844
1. OFF2
p0845
2. OFF2
p0852
Enable operation
X21.3 (+24 V) and X21.4 (ground)
EP terminals enable (pulse enable)
Drive
Parameter/Terminal
Description
p0840
ON/OFF1
p0844
1. OFF2
p0845
2. OFF2
p0848
1. OFF3
p0849
2. OFF3
p0852
Enable operation
X21.3 (+24 V) and X21.4 (ground)
EP terminals enable (pulse enable)
p0864
Infeed enable
p1140
Ramp-function generator enable
p1141
Ramp-function generator Start
p1142
Setpoint enable
References:
SINAMICS S120 Commissioning Manual
/GH2/ Equipment Manual for Booksize Power Units