Adapting the terminal strip
5.5 Analog outputs
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
93
5.5
Analog outputs
Analog output terminals
Changing the function of the analog output
$2
*1'
*1'
CO: rxxyy
p0771[0]
$2
p0771[1]
p0776[0]
p0776[1]
1.
Define the analog output type using parameter
p0776 (e.g. voltage output -10 V … 10 V or
current output 4 mA … 20 mA).
2.
Interconnect parameter p0771 with a
connector output of your choice (e.g. the
actual speed).
Connector outputs are designated with "CO" in
the parameter list of the List Manual.
Defining the analog output type
The inverter offers a series of default settings, which you can select using parameter p0776:
AO 0
Current output (factory setting)
Voltage output
Current output
0 mA … +20 mA
0 V … +10 V
+4 mA … +20 mA
p0776[0] =
0
1
2
AO 1
Current output (factory setting)
Voltage output
Current output
0 mA … +20 mA
0 V … +10 V
+4 mA … +20 mA
p0776[1] =
0
1
2
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
&XUUHQWRXWSXWP$P$
9ROWDJHRXWSXW99
S
S
P$
9
[
S
\
S
[
S
\
S
[
S
\
S
[
S
\
S
Figure 5-3
Examples for scaling characteristics
Содержание SINAMICS G120 CU230P-2