Table 6- 44 Analog value objects
Instance ID Object name
Description
Unit
Area
Access
type
Parameter
AV0
OUTPUT FREQ_Hz Output frequency (Hz)
Hz
-327.68 … 327.67
R
r0024
AV1
OUTPUT
FREQ_PCT
Output frequency (%)
%
-100.0 … 100.0
R
HIW
AV2
OUTPUT SPEED
Motor speed
RPM
-16250 … 16250
R
r0022
AV3
DC BUS VOLT
DC link voltage.
V
0 … 32767
R
r0026
AV4
OUTPUT VOLT
Output voltage
V
0 … 32767
R
r0025
AV5
CURRENT
Motor current
A
0 … 163.83
R
r0027
AV6
TORQUE
Motor torque
Nm
- 325.00 … 325.00
R
r0031
AV7
POWER
Motor power
kW
0 … 327.67
R
r0032
AV8
DRIVE TEMP
Heat-sink temperature
°C
0 … 327.67
R
r0037
AV9
MOTOR TEMP
Measured or calculated motor
temperature
°C
0 … 327.67
R
r0035
AV10
KWH (NR)
Cumulative inverter energy
consumption (cannot be reset!)
kWh
0 … 32767
R
r0039
AV12
INV RUN TIME (R) Motor's operating hours (is
reset by entering "0")
h
0 … 4294967295
W
p0650
AV13
INV Model
Code number of Power Module ---
R
r0200
AV14
INV FW VER
Firmware version
---
R
r0018
AV15
INV POWER
Rated power of the inverter
kW
0 … 327.67
R
r0206
AV16
RPM STPT 1
Inverter's reference speed
RPM
6.0 … 210000
W
p2000
AV17
FREQ STPT PCT
Setpoint 1 (when controlling
via BACnet)
%
-199.99 … 199.99
C
HSW
AV18
ACT FAULT
Fault number of fault due to be
dealt with
---
0 … 32767
R
r0947[0]
AV19
PREV FAULT 1
Fault number of last fault
---
0 … 32767
R
r0947[1]
AV20
PREV FAULT 2
Fault number of last but one
fault
---
0 … 32767
R
r0947[2]
AV21
PREV FAULT 3
Fault number of the third from
last fault
---
0 … 32767
R
r0947[3]
AV22
PREV FAULT 4
Fault number of the fourth from
last fault
---
0 … 32767
R
r0947[4]
AV25
Select Setpoint
Source
Command to select the
setpoint source
---
0 … 32767
W
p1000
AV28
AO1 ACT
Signal from AO 1
mA
-100.0 … 100.0
R
r0774.0
AV29
AO2 ACT
Signal from AO 1
mA
-100.0 … 100.0
R
r0774.1
AV30
MIN SPEED
Minimum speed
RPM
0.000 – 19500.000
W
p1080
AV31
MAX FREQ
Maximum speed
RPM
0.000 … 210000.000 W
p1082
AV32
ACCEL TIME
Rampup time
s
0.00 … 999999.0
W
p1120
AV33
DECEL TIME
Ramp-down time
s
0.00 … 999999.0
W
P1121