Functions
7.9 Application-specific functions
Frequency inverters with Control Units CU230P-2 HVAC, CU230P-2 DP, CU230P-2 CAN
Operating Instructions, 01/2011, FW 4.4, A5E02430659B AD
255
Table 7- 45 Parameters that are required to set the essential service mode
Parameter
Description
Setting the source for the essential service mode
p3880 = 722.3
ESM activation (here, via DI3, high-active)
Signal source for activating the essential service mode
722.x for high active, 723.x for low active
Additional parameters to set the essential service mode
p3881
ESM setpoint source, 0 … 4
p3882
ESM substitute setpoint source
Setpoint should the parameterized ESM setpoint be lost
p3883
ESM direction of rotation
Signal source for direction of rotation in the essential service mode, is not
evaluated when p3881 = 4
p3884
ESM setpoint technology controller
If p3884 is not connected up, then the technology controller uses the main
setpoint corresponding to p2251 = 0.
r3887
ESM: Number of activations and faults
Indicates how frequently ESM has been activated (index 0) and how many faults
occurred during ESM (index 1).
p3888
ESM: Reset the number of activations and faults
p3888 = 1 resets 3887[0] and 3887[1].
r3889
ESM status word
Faults, which are not ignored when operating in the essential service mode
F01000
Internal software error
F01001
Floating Point Exception
F01002
Internal software error
F01003
Time-out for memory access
F01015
Internal software error
F01040
Back up parameters and perform a POWER ON
F01044
Error in description data
F01205
Time slice overflow
F01512
BICO: No scaling
F01662
Error, internal communications
F07901
Drive: Motor overspeed
F30001
Power unit: Overcurrent
F30002
Power unit: DC-link voltage overvoltage
F30003
Power unit: DC-link voltage undervoltage
F30004
Power unit: Overtemperature heatsink inverter
F30005
Power unit: Overload I2t
F30017
Power unit: Hardware current limit has responded too often
F30021
Power unit: Ground fault